Use one ID everywhere
The bay marking, the back office and this form should share one charge point ID. Otherwise a fault reported on bay 12 gets investigated on the wrong charger.
Free form template · Install & commission
A per-charger install and commissioning record for workplace, fleet and multi-site charge point rollouts: where it is, what it is, how it's supplied and protected, what it measured, and who accepted it.
Free 7-day trial · no credit card required
Template
EV charger commissioning checklist
Project and site *
Charge point ID or bay number *
Location type *
Intended use *
Photo of the installed unit and bay *
Polarity and phase rotation *
An EV charger commissioning checklist should record, for each charge point: the site and bay, make, model, serial and rating; the supply circuit and protective devices; the earthing arrangement and any PME measure; test readings with units; RCD and DC fault protection; a test charge; connectivity and smart settings; handover to the customer; and signatures.
Last updated . Facts checked on 30 September 2026 against IET: Code of Practice for Electric Vehicle Charging Equipment Installation, 5th edition and IET Wiring Matters: BS 7671:2018+A1 changes, including section 722.
Who uses it
Electricians and commissioning engineers installing commercial, workplace, fleet or car park charge points, one record per charger.
When
As each charge point is installed and tested, before it is energised for customer use, and again if a unit is replaced.
In Integrio
Build it once in the Form Builder (Office User), attach it to projects, and your team fills it in on iOS or Android, offline if needed.
Free template · integrio.app/forms/ev-charger-commissioning-checklist/EV charger commissioning checklist template
A per-charger install and commissioning record for workplace, fleet and multi-site charge point rollouts: where it is, what it is, how it's supplied and protected, what it measured, and who accepted it.
| Project | Site | Completed by | Date |
The template
5 sections and 36 fields. Copy them into any format, print this page, or set the form up in Integrio.
Enough detail to find this exact unit on a site with forty of them.
Project and siteRequired
Charge point ID or bay numberRequired
Use the same ID as the bay marking and the operator's back office.
Location typeRequired
Intended useRequired
Make and modelRequired
Serial numberRequired
Photograph the rating plate as well.
Rated outputRequired(kW)
ConnectorRequired
Photo of the installed unit and bayRequired
Supplied from (board and circuit)Required
e.g. DB-EV2, way 5 L1–L3.
SupplyRequired
Cable sizeRequired(mm²)
Overcurrent device ratingRequired(A)
RCD and DC fault protectionRequired
Earthing arrangementRequired
PME measure for an outdoor charge point
Record which option of BS 7671 regulation 722.411.4.1 the design uses.
↳ Shown when Earthing arrangement is TN-C-S (PME)
Earth electrode resistance(Ω)
↳ Shown when Earthing arrangement is TT, or PME measure is Earth electrode
Record the reading and its unit, not just a tick.
Continuity of protective conductors (R1 + R2)Required(Ω)
Insulation resistanceRequired(MΩ)
Earth fault loop impedance (Zs)Required(Ω)
Prospective fault currentRequired(kA)
RCD trip time at rated residual currentRequired(ms)
Polarity and phase rotationRequired
Test instrument and serialRequired
Electrical certificate reference
The certificate itself is issued under your own scheme.
Functional checksRequired
| Check | Pass | Fail | N/A |
|---|---|---|---|
| Powers up with no fault codes | ○ | ○ | ○ |
| Test charge with vehicle or EV simulator | ○ | ○ | ○ |
| Starts and stops by app, RFID or plug-in as set up | ○ | ○ | ○ |
| Current limit or load management set to design | ○ | ○ | ○ |
| Connected to the network (4G, Wi-Fi or Ethernet) | ○ | ○ | ○ |
| Showing online in the operator's back office | ○ | ○ | ○ |
| Firmware updated to the version agreed | ○ | ○ | ○ |
Do the Smart Charge Points Regulations apply to this unit?Required
Seller's statement of compliance received
↳ Shown when the Regulations apply
Default off-peak charging hours shown to the owner
The owner can accept, remove or change them.
↳ Shown when the Regulations apply
Fault details and action
↳ Shown when any functional check is Fail
Handed over
Ready for useRequired
What's outstanding
↳ Shown when Ready for use is No
Installer name and signatureRequired
Customer name and signatureRequired
Date commissionedRequired
EV charger commissioning checklist from Integrio, free to use and adapt. Run it on phones, offline, with photos and signatures: integrio.app · Free 7-day trial, no credit card required.
From the field
The bay marking, the back office and this form should share one charge point ID. Otherwise a fault reported on bay 12 gets investigated on the wrong charger.
Serials and part numbers are hard to read once a unit is mounted and sealed, and you'll need them for every warranty claim.
On a mixed site some units are indoors and some aren't. Note which earthing measure each unit relies on, so a later visit doesn't have to work it out again.
A charger can show online and still refuse a vehicle. Finish every record with a real test charge or a simulator test.
Frequently asked questions
Yes. Use the fields on this page however suits you: print them, put them in a spreadsheet, or build them into Integrio so every charger on every site is recorded the same way.
Section 722 does not allow a PME supply to a charge point located outdoors, or one that may charge a vehicle outdoors, unless one of the options in regulation 722.411.4.1 is met: a balanced three-phase installation, an earth electrode, a device that detects a PEN fault, or an equivalent device. Check the current edition of BS 7671 and the IET Code of Practice for the full wording.
Sources: IET Wiring Matters: BS 7671:2018+A1 changes, including section 722, IET: Code of Practice for Electric Vehicle Charging Equipment Installation, 5th edition
They apply to charge points sold in Great Britain for cars and vans, but not to public charge points or rapid charge points of 50 kW or more. Workplace charge points are not treated as public, so they can be in scope. In-scope units need smart functionality, default off-peak charging hours and a randomised delay, and the seller supplies a statement of compliance.
Sources: Smart Charge Points Regulations 2021, regulation 3 (application), The Electric Vehicles (Smart Charge Points) Regulations 2021
No. Integrio records the install, the product data and the commissioning for each charger, and supports aftercare with tickets and maintenance visits. Charging sessions, tariffs and OCPP connections stay in your charge point management system.
Build it once in the Integrio Form Builder, which is on the Office User plan (£65 per user per month), and attach it to the charger product so every unit gets the same testing form. Engineers fill it in on the mobile app on the Field Service User plan (£15 per user per month), offline if the car park has no signal.