Solar PV commissioning sheet template

A commissioning test sheet for each PV string and its inverter: visual inspection, Voc, Isc, polarity, insulation resistance, isolator and inverter checks, and a signed result.

Free 7-day trial · no credit card required

6
Sections
33
Fields
10
Field types

What should a solar PV commissioning sheet include?

For each string: module quantity and rated Voc and Isc, protective device and cable details, measured Voc, Isc and irradiance, a polarity check, insulation resistance positive and negative to earth with the test voltage, earth continuity where fitted, and array isolator and inverter checks with the inverter's make, model and serial number.

Last updated . Facts checked on 30 September 2026 against MCS: MIS 3002 Issue 6.0, The Solar PV Installation Standard (18/03/2026).

Who uses it

The commissioning engineer or electrician testing a PV array, one sheet per string or per inverter.

When

At initial verification after installation, and again at periodic inspection or after a string is repaired.

In Integrio

Build it once in the Form Builder (Office User), attach it to projects, and your team fills it in on iOS or Android, offline if needed.

IntegrioFree template · integrio.app/forms/solar-pv-commissioning-sheet/

Solar PV commissioning sheet template

A commissioning test sheet for each PV string and its inverter: visual inspection, Voc, Isc, polarity, insulation resistance, isolator and inverter checks, and a signed result.

Project
Site
Completed by
Date

The template

What's in the solar pv commissioning sheet?

6 sections and 33 fields. Copy them into any format, print this page, or set the form up in Integrio.

  1. 1.Test details

    1. 1.1

      Installation addressRequired

      Text
    2. 1.2

      Verification typeRequired

      • Initial verification
      • Periodic verification
      Choose one
    3. 1.3

      Test dateRequired

      Date
    4. 1.4

      Tested byRequired

      Text
    5. 1.5

      Test instruments and serial numbersRequired

      Include the calibration due date.

      Text
  2. 2.Inverter and string

    One sheet per string. Scan or type the serials so they sit against the product record.

    1. 2.1

      Inverter make and modelRequired

      Text
    2. 2.2

      Inverter serial numberRequired

      Text
    3. 2.3

      String referenceRequired

      e.g. INV2 / MPPT1 / S3, matching the string on the layout drawing.

      Text
    4. 2.4

      Modules in stringRequired

      Reading
    5. 2.5

      Rated Voc of string (STC)Required(V)

      From the design: module Voc × modules in string.

      Reading
    6. 2.6

      Rated Isc of string (STC)Required(A)

      Reading
    7. 2.7

      String protective device rating(A)

      Where string fuses or breakers are fitted.

      Reading
    8. 2.8

      String cable size(mm²)

      Reading
  3. 3.Visual inspection

    1. 3.1

      InspectionRequired

      CheckPassFailN/A
      Modules undamaged and fixed to the design○○○
      DC connectors matched, crimped with the correct tool, clear of standing water○○○
      DC cables supported and protected○○○
      Enclosures keep their IP rating (bottom entry, one cable per gland)○○○
      DC isolator accessible and labelled○○○
      Warning labels and schematic displayed○○○
      Inverter ventilation clear○○○
      Checklist grid
  4. 4.String tests

    1. 4.1

      Polarity correctRequired

      Check before closing the isolator or connecting the inverter.

      • Pass
      • Fail
      Pass / Fail
    2. 4.2

      Measured VocRequired(V)

      Reading
    3. 4.3

      Measured IscRequired(A)

      Reading
    4. 4.4

      Irradiance at time of testRequired(W/m²)

      Reading
    5. 4.5

      Insulation test voltageRequired(V)

      Reading
    6. 4.6

      Insulation resistance, positive to earthRequired(MΩ)

      Reading
    7. 4.7

      Insulation resistance, negative to earthRequired(MΩ)

      Reading
    8. 4.8

      Earth continuity (where array frame earthing is fitted)(Ω)

      Reading
  5. 5.Isolator and inverter

    1. 5.1

      Array isolator locationRequired

      Text
    2. 5.2

      Array isolator ratingRequired(A)

      Reading
    3. 5.3

      Array isolator functional checkRequired

      • Pass
      • Fail
      Pass / Fail
    4. 5.4

      Arc fault detection enabled (if the inverter has it)

      • Enabled
      • Not available on this inverter
      Choose one
    5. 5.5

      Grid settings / export limit match the DNO connectionRequired

      Record the export limit in the notes if one applies.

      • Yes
      • No
      Yes / No
    6. 5.6

      Inverter functional checkRequired

      Running, exporting, no fault codes.

      • Pass
      • Fail
      Pass / Fail
  6. 6.Result and sign-off

    1. 6.1

      Overall resultRequired

      • Pass
      • Fail
      Pass / Fail
    2. 6.2

      What failed and the action takenRequired

      ↳ Shown when Overall result is Fail

      Notes
    3. 6.3

      Photo of the fault

      ↳ Shown when Overall result is Fail

      Photo
    4. 6.4

      Notes

      Notes
    5. 6.5

      Tested by (signature)Required

      Signature

Solar PV commissioning sheet from Integrio, free to use and adapt. Run it on phones, offline, with photos and signatures: integrio.app · Free 7-day trial, no credit card required.

From the field

How do you get the most from a solar pv commissioning sheet?

01

Record irradiance with every Isc

Isc moves with the sun. A reading with no irradiance next to it can't be compared with the rated figure, or with the same string next year.

02

Compare strings, not just limits

On a commercial roof, identical strings should read alike. A string reading well below its neighbours points to a wiring or module problem in that string; find it before the scaffold comes down.

03

Tie the sheet to the inverter serial

Store results against the inverter and string reference, not just the job. When an O&M ticket comes in years later, the baseline readings are one tap away.

04

Fail it properly

If a reading fails, record what was found and what was done, then retest on a fresh sheet. Overwriting a failed reading hides the history the next engineer needs.

Frequently asked questions

What do people ask about the solar pv commissioning sheet?

Ask our team →

What tests does MCS require for solar PV commissioning?

+

MIS 3002 says the system is commissioned to a documented procedure and inspected and tested to Section 16 of the IET Code of Practice for grid-connected solar PV (excluding 16.4). Its Appendix E model array test report, adapted from BS EN 62446-1, records Voc, Isc, irradiance, polarity, insulation resistance and isolator and inverter checks for each string.

Sources: MCS: MIS 3002 Issue 6.0, The Solar PV Installation Standard (18/03/2026), IET: Code of Practice for Grid-connected Solar Photovoltaic Systems, 2nd Edition

Is this the same as the BS EN 62446-1 test report?

+

It covers the same readings as the model array test report that MCS reproduces from BS EN 62446-1, laid out as a mobile form. IEC 62446-1 also covers inspection criteria and the documentation handed to the customer, so keep the standard itself for the full procedure.

Sources: IEC 62446-1:2016, Grid connected PV systems: documentation, commissioning tests and inspection, MCS: MIS 3002 Issue 6.0, The Solar PV Installation Standard (18/03/2026)

Does this replace the electrical installation certificate?

+

No. This sheet records the PV array tests. The AC side still needs its BS 7671 certification, and the DNO and MCS paperwork is separate.

Is this solar PV commissioning sheet free?

+

Yes. Use the fields on paper, in a spreadsheet, or set it up in Integrio as a testing form on each inverter.

How do I use this template in Integrio?

+

Build it once in the Integrio Form Builder, which is on the Office User plan (£65 per user per month), and attach it to the inverter product so every unit gets the same test form. Engineers fill it in on the mobile app on the Field Service User plan (£15 per user per month), offline on roofs with no signal.