Record irradiance with every Isc
Isc moves with the sun. A reading with no irradiance next to it can't be compared with the rated figure, or with the same string next year.
Free form template · Install & commission
A commissioning test sheet for each PV string and its inverter: visual inspection, Voc, Isc, polarity, insulation resistance, isolator and inverter checks, and a signed result.
Free 7-day trial · no credit card required
Template
Solar PV commissioning sheet
Installation address *
Verification type *
Tested by *
Polarity correct *
Grid settings / export limit match the DNO connection *
Tested by (signature) *
For each string: module quantity and rated Voc and Isc, protective device and cable details, measured Voc, Isc and irradiance, a polarity check, insulation resistance positive and negative to earth with the test voltage, earth continuity where fitted, and array isolator and inverter checks with the inverter's make, model and serial number.
Last updated . Facts checked on 30 September 2026 against MCS: MIS 3002 Issue 6.0, The Solar PV Installation Standard (18/03/2026).
Who uses it
The commissioning engineer or electrician testing a PV array, one sheet per string or per inverter.
When
At initial verification after installation, and again at periodic inspection or after a string is repaired.
In Integrio
Build it once in the Form Builder (Office User), attach it to projects, and your team fills it in on iOS or Android, offline if needed.
Free template · integrio.app/forms/solar-pv-commissioning-sheet/Solar PV commissioning sheet template
A commissioning test sheet for each PV string and its inverter: visual inspection, Voc, Isc, polarity, insulation resistance, isolator and inverter checks, and a signed result.
| Project | Site | Completed by | Date |
The template
6 sections and 33 fields. Copy them into any format, print this page, or set the form up in Integrio.
Installation addressRequired
Verification typeRequired
Test dateRequired
Tested byRequired
Test instruments and serial numbersRequired
Include the calibration due date.
One sheet per string. Scan or type the serials so they sit against the product record.
Inverter make and modelRequired
Inverter serial numberRequired
String referenceRequired
e.g. INV2 / MPPT1 / S3, matching the string on the layout drawing.
Modules in stringRequired
Rated Voc of string (STC)Required(V)
From the design: module Voc × modules in string.
Rated Isc of string (STC)Required(A)
String protective device rating(A)
Where string fuses or breakers are fitted.
String cable size(mm²)
InspectionRequired
| Check | Pass | Fail | N/A |
|---|---|---|---|
| Modules undamaged and fixed to the design | ○ | ○ | ○ |
| DC connectors matched, crimped with the correct tool, clear of standing water | ○ | ○ | ○ |
| DC cables supported and protected | ○ | ○ | ○ |
| Enclosures keep their IP rating (bottom entry, one cable per gland) | ○ | ○ | ○ |
| DC isolator accessible and labelled | ○ | ○ | ○ |
| Warning labels and schematic displayed | ○ | ○ | ○ |
| Inverter ventilation clear | ○ | ○ | ○ |
Polarity correctRequired
Check before closing the isolator or connecting the inverter.
Measured VocRequired(V)
Measured IscRequired(A)
Irradiance at time of testRequired(W/m²)
Insulation test voltageRequired(V)
Insulation resistance, positive to earthRequired(MΩ)
Insulation resistance, negative to earthRequired(MΩ)
Earth continuity (where array frame earthing is fitted)(Ω)
Array isolator locationRequired
Array isolator ratingRequired(A)
Array isolator functional checkRequired
Arc fault detection enabled (if the inverter has it)
Grid settings / export limit match the DNO connectionRequired
Record the export limit in the notes if one applies.
Inverter functional checkRequired
Running, exporting, no fault codes.
Overall resultRequired
What failed and the action takenRequired
↳ Shown when Overall result is Fail
Photo of the fault
↳ Shown when Overall result is Fail
Notes
Tested by (signature)Required
Solar PV commissioning sheet from Integrio, free to use and adapt. Run it on phones, offline, with photos and signatures: integrio.app · Free 7-day trial, no credit card required.
From the field
Isc moves with the sun. A reading with no irradiance next to it can't be compared with the rated figure, or with the same string next year.
On a commercial roof, identical strings should read alike. A string reading well below its neighbours points to a wiring or module problem in that string; find it before the scaffold comes down.
Store results against the inverter and string reference, not just the job. When an O&M ticket comes in years later, the baseline readings are one tap away.
If a reading fails, record what was found and what was done, then retest on a fresh sheet. Overwriting a failed reading hides the history the next engineer needs.
MIS 3002 says the system is commissioned to a documented procedure and inspected and tested to Section 16 of the IET Code of Practice for grid-connected solar PV (excluding 16.4). Its Appendix E model array test report, adapted from BS EN 62446-1, records Voc, Isc, irradiance, polarity, insulation resistance and isolator and inverter checks for each string.
Sources: MCS: MIS 3002 Issue 6.0, The Solar PV Installation Standard (18/03/2026), IET: Code of Practice for Grid-connected Solar Photovoltaic Systems, 2nd Edition
It covers the same readings as the model array test report that MCS reproduces from BS EN 62446-1, laid out as a mobile form. IEC 62446-1 also covers inspection criteria and the documentation handed to the customer, so keep the standard itself for the full procedure.
Sources: IEC 62446-1:2016, Grid connected PV systems: documentation, commissioning tests and inspection, MCS: MIS 3002 Issue 6.0, The Solar PV Installation Standard (18/03/2026)
No. This sheet records the PV array tests. The AC side still needs its BS 7671 certification, and the DNO and MCS paperwork is separate.
Yes. Use the fields on paper, in a spreadsheet, or set it up in Integrio as a testing form on each inverter.
Build it once in the Integrio Form Builder, which is on the Office User plan (£65 per user per month), and attach it to the inverter product so every unit gets the same test form. Engineers fill it in on the mobile app on the Field Service User plan (£15 per user per month), offline on roofs with no signal.